Lightning Controller Rail 3-pin. with NPE 255V - Combined arrester for power systems MCF100-NAR-TT

OBO - MCF100-NAR-TT - Lightning Controller Rail 3-pin. with NPE 255V - Combined arrester for power systems MCF100-NAR-TT
Photo source: fig. possibly similar
Photo source: fig. possibly similar
MCF100-NAR-TT 5096985 4012196608744 EAN/GTIN DE 64419409 WEEE

72,542.08₹ excl. VAT
141,405.82₹ (-48.7% RRP***)

16-17 days* (IND)

Safety and hazard information
Please note that electrotechnical work may only be carried out by qualified electricians or under their guidance and supervision. Observe any deviating country-specific electrical installation standards and regulations and seek advice from a local electrician.In addition, observe more current safety instructions and regulations for the products on the manufacturer's side or the product descriptions and installation instructions on the manufacturer's side.

Devices with a connected load of > 380V/400V require a heavy current connection and may only be connected by an approved electrical company. Devices with a power rating > 12kW require the approval of your grid operator (Germany, other countries may differ).
read more
show less
Lightning Controller Rail 3-pin. m.NPE 255V MCF100-NAR-TT TN system type, TN-C system type, TN-CS... more
Lightning Controller Rail 3-pin. with NPE 255V - Combined arrester for power systems MCF100-NAR-TT – OBO – 5096985 – 4012196608744: Lightning Controller Rail 3-pin. m.NPE 255V MCF100-NAR-TT TN system type, TN-C system type, TN-CS system type, TN-S system type, TT system type, number of poles 4, lightning impulse current (10/350 µs) 25kA, maximum continuous voltage AC 255V, nominal voltage AC 230V , protection level 1.5kV, protection level LN 1.5kV, protection level N-PE 1.5kV, follow current extinguishing capacity 0.1kA, max. conductor cross-section solid (solid/stranded) 35mm², max. conductor cross-section flexible (finely stranded) 35mm², mounting type busbar, size other, optical signaling on the device, test class type 1 and 2, The MCF100-NAR combined arrester type 1+2 for lightning protection equipotential bonding according to VDE 0185-305 (IEC 62305) is suitable for use in the pre-counter area according to VDE-AR-N 4100. Area of application of the MCF100-NAR are buildings with lightning protection or overhead line feed in TN-S and TT systems. It is installed on 40 mm busbars in the connection compartment on the mains side. The protection level of <=1.5 kV protects the end devices in the system. The lightning current discharge capacity is 100 kA (10/350) in total and 25 kA (10/350) per pole, follow current extinguishing up to 50 kA with a max. back-up fuse up to 315 A gL/gG.
... more
Network shape TN yes
Mains form TN-CS yes
Mains form TN-S yes
Network shape TT yes
Lightning impulse current (10/350 µs) 25 kA
Nominal discharge current (8/20) 25 kA
Highest continuous voltage AC 255V
Rated voltage AC 230V
Protection level 1.5 kV
Protection level LN 1.5 kV
Follow current extinguishing capability 0.1 kA
Mounting Bus bar
Size other
Signaling on the device optical
IP protection) IP20

Rate item

(0 reviews)
Read, write and discuss reviews... more
Customer review for "Lightning Controller Rail 3-pin. with NPE 255V - Combined arrester for power systems MCF100-NAR-TT"
Write a review
Evaluations will be activated after verification.
Please enter these characters in the following text field.

The fields marked with * are required.