Combined arrester for power systems V50-2+NPE-280

OBO - V50-2+NPE-280 - Combined arrester for power systems V50-2+NPE-280
Photo source: fig. possibly similar
Photo source: fig. possibly similar
V50-2+NPE-280 5093524 4012196159680 EAN/GTIN

20,805.70₹ incl. VAT

11-12 days* (DEU)

Number of poles 3, Highest continuous voltage AC 280V, Rated voltage AC 230V, Protection level... more
Combined arrester for power systems V50-2+NPE-280 – OBO – 5093524 – 4012196159680: Number of poles 3, Highest continuous voltage AC 280V, Rated voltage AC 230V, Protection level 1.3 kV, Protection level L-N 1.3 kV, Size 3 TE, Remote signaling no, Signaling on the device optical, Test class Type 1 and 2, Extinguishing no

Extended product description for Combined arrester for power systems

Additional product description

Solid functionality with excellent practical value: The item on offer here is made by OBO. We have listed this product under item no. EB15903169. In the eibabo® shop, the product is listed in the Combined arresters - eletric product group in the Electrical material catalog. This item offers outstanding value for money. This is a popular item at eibabo®, it receives a lot of search traffic and purchases. Unfortunately, this item does not have high-resolution 3D views yet. Our in-house 3D photography studio is working hard to produce images for this item. Order this product from OBO now. You can find an overview with more data and information about the product here:

  • Manufacturer item number: V50-2+NPE-280
  • Manufacturer order number: 5093524
  • EAN/GTIN: 4012196159680
  • Customs tariff number: 85363030
  • Item’s country of origin: Hungary

Special features and characteristics

  • Number of poles: 3
  • Highest continuous voltage AC: 280V
  • Rated voltage AC: 230V
  • Protection level: 1.3 kV
  • Protection level L-N: 1.3 kV
  • Size: 3 TE
  • Signaling on the device: optical
  • Test class: Type 1 and 2

Product recommendations, optional accessories & alternative products

Frequently purchased items

Our customers often purchase the following popular items in addition to the Combined arrester for power systems, OBO, V50-2+NPE-280:

Recommendations for other relevant products

On eibabo®, the following popular products are searched for and purchased along with the Combined arrester for power systems:

The item Combined arrester for power systems is frequently found in searches for the following topics: BC arrester, BC combination Blitzductor, as well as lightning protection module. You can also find other similar products when you search for Combined arresters - eletric. Check out other items from this manufacturer at the following link: OBO.

Combined arrester for power systems Number of poles 3, Lightning impulse current (10/350 µs) 12,5kA, Max. continuous voltage AC 280V, Nominal voltage AC 230V, Voltage protection level 1,3kV, Voltage protection level L-N 1,3kV, Max. conductor cross section solid (solid, stranded) 35mm², Max. conductor cross section flexible (fine-strand) 25mm², Mounting method DIN rail (top hat rail) 35 mm, Construction size 3 modular spacing, Signalling at the device Optic, Test class Type 1 + 2

... more
System configuration DC no
System configuration IT no
System configuration TN yes
System configuration TN-C no
System configuration TN-CS yes
System configuration TN-S yes
System configuration TT yes
System configuration other no
Number of poles 3
Lightning impulse current (10/350 µs) 12.5 kA
Highest continuous voltage AC 280V
Rated voltage AC 230V
Protection level 1.3 kV
Protection level L-N 1.3 kV
Protection level N-PE 1.5 kV
Follow current extinguishing capability 0.1 kA
Mounting DIN rail TH35
Size 3 TE
Remote signaling no
Signaling on the device optical
Test class Type 1 and 2
Extinguishing no
Integrated back-up fuse no